Model name | THT-400-A/R |
Input | Wet bulb input: RTD, Pt100 3-wire system, 0 to 100℃ (allowable input lead wire resistance: 10Ω or less per wire) Dry bulb input: RTD, Pt100 3-wire system, 0 to 100℃ (allowable input lead wire resistance: 10Ω or less per wire) RTD, Pt100 3-wire system, 0 to 200℃ (allowable input lead wire resistance: 10Ω or less per wire) (For Dry bulb input, 0 to 100℃ is a standard feature 0 to 200℃ can be switched by the internal jumper of the unit) |
Output | Temperature output:Outputs below corresponding to the dry bulb input temperature of 0 to 100℃ or 0 to 200℃. 0 to 20mA DC or 4 to 20mA DC, Load resistance maximum 550Ω. Humidity output: Outputs below corresponding to the relative humidity 0 to *RH by using dry bulb input temperature 0 to 100℃ and wet bulb input temperature 0 to 100℃. 0 to 20mA DC or 4 to 20mA DC, Load resistance maximum 550Ω |
Conversion accuracy | Temperature output: Within converted temperature ±1.0℃ Humidity output: Within ±3% of full scale |
Input sampling period | 0.5 seconds |
Output resolution | 1/8000 |
Supply voltage | 100 to 240V AC, 50/60Hz |
Power consumption | Approx. 5VA |
Environment | Ambient temperature: 0 to 50℃ Ambient humidity: 35 to 85%RH(non-condensing) |
Case Material-Color | Flame resistant resin Color: Light gray |
External dimensions | 75×106.2×111mm(W×H×D) |
Mounting method | Mounting by the frame with screws inside the control panel (3mm screw for 4 positions) Mounting angle: Nickel plated steel sheet(SPCC) |
Weight | Approx. 200g |
Option[TC] | Electric shock protection terminal cover |