产品简介

SIPLUSS7-300CPU314C-2PN/DP,CPU 314C-2 DP 是紧凑型 CPU,适合安装在分布式结构中。通过其扩展工作存储器,该紧凑型CPU也适用于中等规模的应用。集成的数字量和模拟量输入和输出可与过程信号直接连接。集成的 的PROFIBUS DP 主站/从站以及 PROFINET IO 控制器/I-设备接口,用于 PROFIBUS 和 PROFINET 的分布式连接。

详细介绍

SIPLUSS7-300CPU314C-2PN/DP,S7-300CPU314C-2PN/DP,西门子S7-300CPU314C-2PN/DP,CPU314C-2PN/DP,西门子CPU314C-2PN/DP

订货号:6AG1314-6EH04-7AB0

SIPLUS S7-300 CPU314C-2PN/DP WITH CONFORMAL COATING -25 ... +70 DEGREES C BASED ON 6ES7314-6EH04-0AB0 . COMPACT CPU WITH 192 KBYTE WORKING MEMORY, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, INTEGRATED 24V DC POWER SUPPLY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED

德国* 现货销售 质保一年 欢迎询价

SIEMENS上海翰粤自动化系统有限公司

代理销售:西门子PLC模块,S7-200系列,S7-300系列,S7-400系列,S7-1200系列,ET200系列,西门子变频器,西门子触摸屏,西门子低压电器,西门子软启动器,西门子DP总线电缆,西门子DP总线连接器,西门子CP通讯卡,西门子伺服,西门子数控系统及停产备件

 

 

CPU 的运行需要 SIMATIC 微型存储卡。

注:

SIPLUS extreme 产品基于 SIMATIC 标准产品。此处的内容摘自相关标准产品。增加了与 SIPLUS extreme 相关的信息。

SIPLUSS7-300CPU314C-2PN/DP  技术规格

CPU 314C-2 DP 是紧凑型 CPU,适合安装在分布式结构中。通过其扩展工作存储器,该紧凑型CPU也适用于中等规模的应用。集成的数字量和模拟量输入和输出可与过程信号直接连接。集成的 的PROFIBUS DP 主站/从站以及 PROFINET IO 控制器/I-设备接口,用于 PROFIBUS 和 PROFINET 的分布式连接。这使得 CPU 314C-2 PN/DP 可作为进行快速处理的分布式单元使用,也可作为 PROFIBUS 和 PROFINET 系统中具有低端现场总线系统的上位控制器。

集成技术工程的其他用途包括:

 设计

CPU 314C-2 DP 安装有:

 功能

可参数化的特性

可以使用 STEP 7 对 S7 的组态、属性以及CPU的响应进行参数设置:

显示功能与信息功能

集成的通讯功能

集成功能

 技术规格

Order number

6AG1314-6EH04-7AB0

 

SIPLUS S7-300 CPU314C-2PN/DP

General information

 

Engineering with

 

  • ● Programming package

STEP7 V5.5 or higher with HSP191

Supply voltage

 

Rated value (DC)

 

  • ● 24 V DC

Yes

Power loss

 

Power loss, typ.

14 W

Memory

 

Work memory

 

  • ● integrated

192 kbyte

  • ● Size of retentive memory for retentive data blocks

64 kbyte

Load memory

 

  • ● Plug-in (MMC), max.

8 Mbyte

CPU processing times

 

for bit operations, typ.

0.06 µs

for word operations, typ.

0.12 µs

for fixed point arithmetic, typ.

0.16 µs

for floating point arithmetic, typ.

0.59 µs

Counters, timers and their retentivity

 

S7 counter

 

  • ● Number

256

IEC counter

 

  • ● present

Yes

S7 times

 

  • ● Number

256

IEC timer

 

  • ● present

Yes

Data areas and their retentivity

 

Flag

 

  • ● Number, max.

256 byte

Address area

 

I/O address area

 

  • ● Inputs

2 048 byte

  • ● Outputs

2 048 byte

Process image

 

  • ● Inputs, adjustable

2 048 byte

  • ● Outputs, adjustable

2 048 byte

Time of day

 

Clock

 

  • ● Hardware clock (real-time clock)

Yes

Operating hours counter

 

  • ● Number

1

Digital inputs

 

integrated channels (DI)

24

Digital outputs

 

integrated channels (DO)

16

Analog inputs

 

integrated channels (AI)

5; 4 x current/voltage, 1 x resistance

Input ranges

 

  • ● Voltage

Yes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ

  • ● Current

Yes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω

  • ● Resistance thermometer

Yes; Pt 100 / 10 MΩ

  • ● Resistance

Yes; 0 Ω to 600 Ω / 10 MΩ

Analog outputs

 

integrated channels (AO)

2

Output ranges, voltage

 

  • ● 0 to 10 V

Yes

  • ● -10 V to +10 V

Yes

Output ranges, current

 

  • ● 0 to 20 mA

Yes

  • ● -20 mA to +20 mA

Yes

  • ● 4 mA to 20 mA

Yes

1. Interface

 

Interface type

Integrated RS 485 interface

Physics

RS 485

Functionality

 

  • ● MPI

Yes

  • ● DP master

Yes

  • ● DP slave

Yes

  • ● Point-to-point connection

No

DP master

 

  • ● Number of DP slaves, max.

124

2. Interface

 

Interface type

PROFINET

Physics

Ethernet RJ45

Number of ports

2

Functionality

 

  • ● MPI

No

  • ● DP master

No

  • ● DP slave

No

  • ● PROFINET IO Controller

Yes; Also simultaneously with IO-Device functionality

  • ● PROFINET IO Device

Yes; Also simultaneously with IO Controller functionality

  • ● PROFINET CBA

Yes

PROFINET IO Controller

 

  • ● Number of connectable IO Devices for RT, max.

128

  • ● Number of IO Devices with IRT and the option "high flexibility"

128

  • ● Number of IO Devices with IRT and the option "high performance", max.

64

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFINET only

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • ● supported

Yes

S7 basic communication

 

  • ● supported

Yes

S7 communication

 

  • ● supported

Yes

S5 compatible communication

 

  • ● supported

Yes; via CP and loadable FC

Open IE communication

 

  • ● TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • — Number of connections, max.

8

  • ● ISO-on-TCP (RFC1006)

Yes; via integrated PROFINET interface and loadable FBs

  • — Number of connections, max.

8

  • ● UDP

Yes; via integrated PROFINET interface and loadable FBs

  • — Number of connections, max.

8

Web server

 

  • ● supported

Yes

Number of connections

 

  • ● overall

12

Integrated Functions

 

Number of counters

4; See "Technological Functions" manual

Counting frequency (counter) max.

60 kHz

Frequency measurement

Yes

Number of frequency meters

4; up to 60 kHz (see "Technological Functions" manual)

controlled positioning

Yes

integrated function blocks (closed-loop control)

Yes; PID controller (see "Technological Functions" manual)

PID controller

Yes

Number of pulse outputs

4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)

Limit frequency (pulse)

2.5 kHz

Ambient conditions

 

Ambient temperature during operation

 

  • ● min.

-25 °C; = Tmin

  • ● max.

70 °C; = Tmax

Extended ambient conditions

 

  • ● relative to ambient temperature-atmospheric pressure-installation altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

  • — With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

 

  • — against biologically active substances / conformity with EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!

  • — against chemically active substances / conformity with EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — against mechanically active substances / conformity with EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Configuration

 

Programming

 

Programming language

 

  • — LAD

Yes

  • — FBD

Yes

  • — STL

Yes

  • — SCL

Yes

  • — CFC

Yes

  • — GRAPH

Yes

  • — HiGraph®

Yes

Know-how protection

 

  • ● User program protection/password protection

Yes

  • ● Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

120 mm

Height

125 mm

Depth

130 mm

Weights

 

Weight, approx.

730 g

西门子S7-300宽温型CPU  技术规格

以下 SIPLUS S7-300 标准型 CPU 可在恶劣环境条件下使用:

SIPLUS S7-300 紧凑型 CPU 可在以下恶劣环境条件下使用:

 