西门子/SIEMENS 品牌
代理商厂商性质
上海市所在地
SIPLUSS7-300CPU314C-2PN/DP,S7-300CPU314C-2PN/DP,西门子S7-300CPU314C-2PN/DP,CPU314C-2PN/DP,西门子CPU314C-2PN/DP
订货号:6AG1314-6EH04-7AB0 SIPLUS S7-300 CPU314C-2PN/DP WITH CONFORMAL COATING -25 ... +70 DEGREES C BASED ON 6ES7314-6EH04-0AB0 . COMPACT CPU WITH 192 KBYTE WORKING MEMORY, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, INTEGRATED 24V DC POWER SUPPLY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED |
德国* 现货销售 质保一年 欢迎询价
SIEMENS上海翰粤自动化系统有限公司
代理销售:西门子PLC模块,S7-200系列,S7-300系列,S7-400系列,S7-1200系列,ET200系列,西门子变频器,西门子触摸屏,西门子低压电器,西门子软启动器,西门子DP总线电缆,西门子DP总线连接器,西门子CP通讯卡,西门子伺服,西门子数控系统及停产备件
CPU 的运行需要 SIMATIC 微型存储卡。
注:
SIPLUS extreme 产品基于 SIMATIC 标准产品。此处的内容摘自相关标准产品。增加了与 SIPLUS extreme 相关的信息。
SIPLUSS7-300CPU314C-2PN/DP 技术规格
CPU 314C-2 DP 是紧凑型 CPU,适合安装在分布式结构中。通过其扩展工作存储器,该紧凑型CPU也适用于中等规模的应用。集成的数字量和模拟量输入和输出可与过程信号直接连接。集成的 的PROFIBUS DP 主站/从站以及 PROFINET IO 控制器/I-设备接口,用于 PROFIBUS 和 PROFINET 的分布式连接。这使得 CPU 314C-2 PN/DP 可作为进行快速处理的分布式单元使用,也可作为 PROFIBUS 和 PROFINET 系统中具有低端现场总线系统的上位控制器。
集成技术工程的其他用途包括:
设计
CPU 314C-2 DP 安装有:
功能
可参数化的特性
可以使用 STEP 7 对 S7 的组态、属性以及CPU的响应进行参数设置:
显示功能与信息功能
集成的通讯功能
集成功能
技术规格
Order number | 6AG1314-6EH04-7AB0 | |
---|---|---|
| SIPLUS S7-300 CPU314C-2PN/DP | |
General information |
| |
Engineering with |
| |
| STEP7 V5.5 or higher with HSP191 | |
Supply voltage |
| |
Rated value (DC) |
| |
| Yes | |
Power loss |
| |
Power loss, typ. | 14 W | |
Memory |
| |
Work memory |
| |
| 192 kbyte | |
| 64 kbyte | |
Load memory |
| |
| 8 Mbyte | |
CPU processing times |
| |
for bit operations, typ. | 0.06 µs | |
for word operations, typ. | 0.12 µs | |
for fixed point arithmetic, typ. | 0.16 µs | |
for floating point arithmetic, typ. | 0.59 µs | |
Counters, timers and their retentivity |
| |
S7 counter |
| |
| 256 | |
IEC counter |
| |
| Yes | |
S7 times |
| |
| 256 | |
IEC timer |
| |
| Yes | |
Data areas and their retentivity |
| |
Flag |
| |
| 256 byte | |
Address area |
| |
I/O address area |
| |
| 2 048 byte | |
| 2 048 byte | |
Process image |
| |
| 2 048 byte | |
| 2 048 byte | |
Time of day |
| |
Clock |
| |
| Yes | |
Operating hours counter |
| |
| 1 | |
Digital inputs |
| |
integrated channels (DI) | 24 | |
Digital outputs |
| |
integrated channels (DO) | 16 | |
Analog inputs |
| |
integrated channels (AI) | 5; 4 x current/voltage, 1 x resistance | |
Input ranges |
| |
| Yes; ±10 V / 100 kΩ; 0 V to 10 V / 100 kΩ | |
| Yes; ±20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω | |
| Yes; Pt 100 / 10 MΩ | |
| Yes; 0 Ω to 600 Ω / 10 MΩ | |
Analog outputs |
| |
integrated channels (AO) | 2 | |
Output ranges, voltage |
| |
| Yes | |
| Yes | |
Output ranges, current |
| |
| Yes | |
| Yes | |
| Yes | |
1. Interface |
| |
Interface type | Integrated RS 485 interface | |
Physics | RS 485 | |
Functionality |
| |
| Yes | |
| Yes | |
| Yes | |
| No | |
DP master |
| |
| 124 | |
2. Interface |
| |
Interface type | PROFINET | |
Physics | Ethernet RJ45 | |
Number of ports | 2 | |
Functionality |
| |
| No | |
| No | |
| No | |
| Yes; Also simultaneously with IO-Device functionality | |
| Yes; Also simultaneously with IO Controller functionality | |
| Yes | |
PROFINET IO Controller |
| |
| 128 | |
| 128 | |
| 64 | |
Isochronous mode |
| |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFINET only | |
Communication functions |
| |
PG/OP communication | Yes | |
Data record routing | Yes | |
Global data communication |
| |
| Yes | |
S7 basic communication |
| |
| Yes | |
S7 communication |
| |
| Yes | |
S5 compatible communication |
| |
| Yes; via CP and loadable FC | |
Open IE communication |
| |
| Yes; via integrated PROFINET interface and loadable FBs | |
| 8 | |
| Yes; via integrated PROFINET interface and loadable FBs | |
| 8 | |
| Yes; via integrated PROFINET interface and loadable FBs | |
| 8 | |
Web server |
| |
| Yes | |
Number of connections |
| |
| 12 | |
Integrated Functions |
| |
Number of counters | 4; See "Technological Functions" manual | |
Counting frequency (counter) max. | 60 kHz | |
Frequency measurement | Yes | |
Number of frequency meters | 4; up to 60 kHz (see "Technological Functions" manual) | |
controlled positioning | Yes | |
integrated function blocks (closed-loop control) | Yes; PID controller (see "Technological Functions" manual) | |
PID controller | Yes | |
Number of pulse outputs | 4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual) | |
Limit frequency (pulse) | 2.5 kHz | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| -25 °C; = Tmin | |
| 70 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
| |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Configuration |
| |
Programming |
| |
Programming language |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Know-how protection |
| |
| Yes | |
| Yes; With S7 block Privacy | |
Dimensions |
| |
Width | 120 mm | |
Height | 125 mm | |
Depth | 130 mm | |
Weights |
| |
Weight, approx. | 730 g |
西门子S7-300宽温型CPU 技术规格
以下 SIPLUS S7-300 标准型 CPU 可在恶劣环境条件下使用:
SIPLUS S7-300 紧凑型 CPU 可在以下恶劣环境条件下使用: