智能制造网

登录

电气设备/工业电器电源模块电源

倍加福现货接近开关传感器 模块VBA-4E4A-G11-ZAJ/EA2L-F连接电缆全网

供应商:
上海桂伦自动化设备有限公司
企业类型:
经销商

产品简介

倍加福现货接近开关传感器 模块VBA-4E4A-G11-ZAJ/EA2L-F连接电缆全网
德国P+F编码器,传感器 接近开关现货*-*桂伦!
上海桂伦 工作
倍加福传感器代理现货

详细信息

倍加福现货接近开关传感器 模块VBA-4E4A-G11-ZAJ/EA2L-F连接电缆全网

倍加福现货接近开关传感器 模块VBA-4E4A-G11-ZAJ/EA2L-F连接电缆全网

产品阐述
G11 module
4 inputs and 4 outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification≥ V3.0
UL File NumberE223772
Functional safety related parameters
MTTFd120 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: sensor supply i.e. overload or lead interruption outputs
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTswitching state (output); 4 LED yellow/red
yellow: output active
red: output overload or lead interruption
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 240 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC 
option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage12 ... 31 V
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
 0 (unattenuated)≤ 3 mA
 1 (attenuated)≥ 5 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current2 A per output
TB ≤ 40 °C: 6 A total
TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A
Voltage≥ (UAUX - 0.5 V)
Galvanic isolation
Input/Outputsafe isolation, rated insulation voltage 40 V DC
Output/AS-Interfacesafe isolation, rated insulation voltage 40 V DC
Compliance with standards and directives
Directive conformity 
 EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity 
 Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
 Emitted interferenceEN 61000-6-4:2007
 InputEN 61131-2:2007
 Degree of protectionEN 60529:2000
 Fieldbus standardEN 50295:1999, IEC 62026-2:2006
Programming instructions
ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
Data bits (function via AS-Interface)input output
 D0IN1 O1
 D1IN2 O2
 D2IN3 O3
 D3IN4 O4
Parameter bits (programmable via AS-i)function
 P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
 P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
 P2Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
 P3not used
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: AS-Interface flat cable 
Inputs/outputs: M12 round connector
Material 
 HousingPBT PC
 Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
MountingMounting plate
在线询价