产品简介

AS-Interface sensor/actuator module VBA-4E-KE-ZEJQ
德国P+F模块,现货*-*桂伦!订购:
上海桂伦涂 工作
VBA-4E-KE-ZEJQ 倍加福模块全网*现货

详细信息

倍加福模块全网*现货

倍加福模块全网*现货

参数表节选:的技术参数 VBA-4E-KE-ZEJQ

产品阐述
KE switch cabinet module
4 inputs (PNP)
General specifications
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification≥ V2.0
UL File NumberE223772
Indicators/operating means
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED INswitching state (input); 4 LED yellow
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA (without sensors) / max. 180 mA
Protection classIII
Surge protectionUEXT, Ue: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity≤ 150 mA, overload- and short-circuit protected (INT)
Input current≤ 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
 0 (unattenuated)≤ 3 mA
 1 (attenuated)≥ 5 mA
Signal delay< 1 ms (input/AS-Interface)
Compliance with standards and directives
Directive conformity 
 EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity 
 Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
 Emitted interferenceEN 61000-6-4:2007
 InputEN 61131-2:2004
 Degree of protectionEN 60529:2000
 Fieldbus standardEN 50295:1999, IEC 62026-2:2006
Programming instructions
ProfileS-0.A.0
IO code0
ID codeA
ID1 code7
ID2 code0
Data bits (function via AS-Interface)input output
 D0IN1
 D1IN2
 D2IN3
 D3IN4
Parameter bits (programmable via AS-i)function
 P0not used
 P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
 P2Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
 P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material 
 HousingPA 66-FR
Mass150 g
MountingDIN mounting rail
Tightening torque of clamping screws0.5 Nm ... 0.6 Nm